Transformer Size Calculator — kVA, FLA and Protection

Size a dry-type transformer from a connected load, get the standard kVA rating, and see full-load currents and primary protection.

Transformer sizing calculator

Code reference. Transformer overcurrent protection follows NEC 450.3(B). For transformers with a primary current of 9 A or more, primary-only protection is permitted at up to 125% of primary full-load current. Transformers are rated in kVA, not kW, so the load must be converted using its power factor before comparing it with a standard rating.

Why a transformer is rated in kVA

The losses inside a transformer come from two sources: resistive losses in the windings, which depend on current, and core losses, which depend on voltage. Neither depends on the phase relationship between them. That means the heating is set by the product of volts and amps — apparent power — rather than by the real power delivered.

The practical consequence is that a 75 kVA transformer can deliver 75 kW to a resistive load, but only 60 kW to a load at 0.8 power factor, because 60 ÷ 0.8 = 75 kVA. Sizing from a load schedule that lists kW without a power factor is a common way to end up with an undersized transformer.

Standard kVA ratings

Rating (kVA)Typical use208 V three-phase FLA480 V three-phase FLA
15Small commercial, one suite42 A18 A
30Small office or retail83 A36 A
45125 A service at 208 V125 A54 A
75Small industrial, light process208 A90 A
112.5200 A service at 208 V312 A135 A
150Light industrial416 A180 A
225Medium industrial625 A271 A
300Larger industrial833 A361 A
500Heavy industrial1,388 A602 A

Secondary current is what sets your panel bus rating, so 45 kVA at 208 V producing exactly 125 A is why that pair appears so often in commercial fit-outs.

Two worked examples

1. A light industrial load of 65 kW at 0.85 power factor

Apparent power is 65 ÷ 0.85 = 76.5 kVA. With a 25% growth margin the design figure is 95.6 kVA, so the standard size chosen is 112.5 kVA. Its 208 V secondary full-load current is 312 A, which sets the minimum main bus rating of the downstream panel. Primary protection at 125% of the 480 V primary current of 135 A gives about 169 A.

2. A 40 kW resistive heating load at 0.98

Apparent power is 40 ÷ 0.98 = 40.8 kVA. With a 20% margin that is 49 kVA, so a 50 kVA unit would be marginal and 75 kVA is the sensible standard choice. This example shows how much the power factor changes the outcome: at 0.7 the same 40 kW would need 57 kVA at unity growth, and 68 kVA with the same 20% margin.

What the calculation does not cover

How this calculator is verified

Standard kVA ratings follow the commonly manufactured dry-type sizes. Full-load currents are derived directly from the kVA rating and voltage using the standard three-phase formula, and protection sizing follows NEC 450.3(B) at 125% of primary full-load current.

  • NFPA 70, National Electrical Code — Article 450 (transformers), Article 430 (motors), Article 220 (load calculation).
  • NEMA ST 20 — dry-type transformer standards, including the standard kVA and voltage ratings.
  • UL — UL 1561 for dry-type general purpose transformers.

Standard ratings and worked examples last verified: 19 September 2026.

FAQ

How do I size a transformer?

Convert the connected load to kVA by dividing the real power in kW by the power factor, add a growth margin, then select the next standard kVA rating above that figure. Never round down to the nearest standard size.

Why are transformers rated in kVA instead of kW?

Because transformer heating depends on current and voltage independently of the phase relationship between them. Resistive winding losses depend on current and core losses depend on voltage, so apparent power determines the thermal limit regardless of the load power factor.

How do I calculate transformer full-load current?

For three-phase, amps equal kVA times 1000 divided by the square root of 3 times the line voltage. For single-phase, amps equal kVA times 1000 divided by the voltage. A 75 kVA transformer at 480 V three-phase carries 90 A.

What size transformer for a 200 amp service?

At 208 V three-phase, 200 A corresponds to about 72 kVA, so a 75 kVA transformer is the standard choice. At 240 V single-phase, 200 A is 48 kVA, making 50 kVA the nearest standard size.

How much growth margin should I allow?

Twenty to twenty-five percent is typical for commercial and light industrial work where some future load growth is plausible. Where the load is well understood and unlikely to change, ten percent is defensible, but transformers are difficult and disruptive to replace, so erring upward is usually cheaper in the long run.

What is a K-rated transformer?

A transformer designed to tolerate harmonic currents without overheating. Standard transformers are rated for linear loads; where a significant share of the load consists of variable frequency drives or switch-mode power supplies, harmonic losses concentrate in the windings and a K-rated unit is specified instead.

Does the power factor affect transformer sizing?

Yes, substantially. The same real load needs a larger transformer at a lower power factor. A 100 kW load requires 105 kVA at 0.95 but 143 kVA at 0.70, which is a difference of nearly two standard sizes.

What size primary protection does a transformer need?

Under NEC 450.3(B), for a transformer with a primary current of 9 A or more, protection at up to 125% of primary full-load current is permitted where only primary protection is provided. Where both primary and secondary protection are used, the percentages change. Always confirm the rule that applies to your configuration.

Should I use a single large transformer or several smaller ones?

Several smaller units closer to their loads reduce secondary cable lengths, reduce fault current at any one point, and give some redundancy. A single large unit is cheaper to buy and easier to maintain. The decision usually comes down to distribution losses against capital cost.

More electrical tools

Have a suggestion?

Missing a feature or found something off? Tell us — user suggestions decide what we build next.