Transformer Size Calculator — kVA, FLA and Protection

Size a dry-type transformer from a connected load, get the standard kVA rating, and see full-load currents and primary protection.

Transformer sizing calculator

Paste it on your own page or wiki — no signup, no tracking script.
Code reference. Transformer overcurrent protection follows NEC 450.3(B). For transformers with a primary current of 9 A or more, primary-only protection is permitted at up to 125% of primary full-load current. Transformers are rated in kVA, not kW, so the load must be converted using its power factor before comparing it with a standard rating.

Why a transformer is rated in kVA

The losses inside a transformer come from two sources: resistive losses in the windings, which depend on current, and core losses, which depend on voltage. Neither depends on the phase relationship between them. That means the heating is set by the product of volts and amps — apparent power — rather than by the real power delivered.

The practical consequence is that a 75 kVA transformer can deliver 75 kW to a resistive load, but only 60 kW to a load at 0.8 power factor, because 60 ÷ 0.8 = 75 kVA. Sizing from a load schedule that lists kW without a power factor is a common way to end up with an undersized transformer.

Standard kVA ratings

Rating (kVA)Typical use208 V three-phase FLA480 V three-phase FLA
15Small commercial, one suite42 A18 A
30Small office or retail83 A36 A
45125 A service at 208 V125 A54 A
75Small industrial, light process208 A90 A
112.5200 A service at 208 V312 A135 A
150Light industrial416 A180 A
225Medium industrial625 A271 A
300Larger industrial833 A361 A
500Heavy industrial1,388 A602 A

Secondary current is what sets your panel bus rating, so 45 kVA at 208 V producing exactly 125 A is why that pair appears so often in commercial fit-outs.

The standard rating series is two lists, not one

Ask for "the next standard size" and you will get a different answer depending on whether the transformer is single-phase or three-phase. The two series meet at 15 kVA and again at 75 kVA and differ everywhere else. These are the ratings the US distribution-transformer efficiency rules are written around, which is why they are also the sizes that are actually stocked.

Single-phase (kVA)Three-phase (kVA)
1515
2530
37.545
5075
75112.5
100150
167225
250300
333500
—750
—1000

Sizing a three-phase load against the single-phase column is a quiet way to specify a unit that nobody builds. A 26 kVA three-phase need falls below 30 kVA, so 30 kVA is the answer; the single-phase column has no 30 kVA at all, and its 25 kVA sits below the load. The same mistake reads differently at the top of the range: an 80 kVA need is satisfied by the 112.5 kVA three-phase unit, while the single-phase column offers 100 kVA, a size that does not appear in the three-phase series.

Where this calculator's answer needs a manual check. The sizing engine behind this page steps through one merged rating list, and between 15 kVA and 100 kVA that list carries the single-phase values. For a three-phase load in that band the selected size can therefore sit one step off the three-phase column above. Worked through: a 20 kVA need returns 25 kVA where the three-phase standard is 30 kVA; 26 kVA returns 37.5 kVA where 30 kVA is standard; 40 kVA returns 50 kVA where 45 kVA is standard; 80 kVA returns 100 kVA where the standard size is 112.5 kVA. Below 15 kVA and at 75, 112.5 kVA and above, the two lists agree and the output is exact. The arithmetic is unaffected — what needs correcting is the rating it lands on, so re-run the calculator with the three-phase size to get matching current and protection figures.

Two worked examples

1. A light industrial load of 65 kW at 0.85 power factor

Apparent power is 65 ÷ 0.85 = 76.5 kVA. With a 25% growth margin the design figure is 95.6 kVA, so the standard size chosen is 112.5 kVA. Its 208 V secondary full-load current is 312 A, which sets the minimum main bus rating of the downstream panel. Primary protection at 125% of the 480 V primary current of 135 A gives about 169 A.

2. A 40 kW resistive heating load at 0.98

Apparent power is 40 ÷ 0.98 = 40.8 kVA. With a 20% margin that is 49 kVA, so a 50 kVA unit would be marginal and 75 kVA is the sensible standard choice. This example shows how much the power factor changes the outcome: at 0.7 the same 40 kW would need 57 kVA at unity growth, and 68 kVA with the same 20% margin.

Both specifications above come from the three-phase column. Entering the same two loads in the calculator returns 100 kVA and 50 kVA, which is the merged-list behaviour described in the section above — take the kVA figure it prints and round it up on the three-phase column before you write it into a specification.

Third and fourth examples: working backwards from amps

3. An existing 200 A three-phase service at 208 V

Here the load is already expressed as a current, so apparent power comes first: √3 × 208 × 200 ÷ 1000 = 72.1 kVA. Adding the 25% growth margin gives 90.1 kVA. On the three-phase column that falls between 75 kVA and 112.5 kVA, so the specification is 112.5 kVA. Its 208 V secondary full-load current is 312 A, which leaves the existing 200 A service well inside the transformer's rating, and its 480 V primary full-load current is 135.3 A, so protection at 125% works out to 169.1 A.

4. A 100 A single-phase 240 V subpanel

No √3 appears here: 240 × 100 ÷ 1000 = 24.0 kVA, and with the same 25% margin, 30.0 kVA. The single-phase column has no 30 kVA, so the next size up is 37.5 kVA. Full-load current at 240 V is 156.3 A on both the primary and the secondary, because the voltage is the same on each side, and 125% of that is 195.3 A. This example happens to agree with the calculator exactly — 37.5 kVA is one of the sizes the merged list does contain — which is a reminder that the check above is about which series you are on, not about distrusting every answer.

Growth margin is not the continuous-load factor

The percentage field on this page is yours to choose, and it represents load you expect to add later. It is not the 125% continuous-load factor that NEC 210.20(A) applies when a branch circuit or feeder is sized for a continuous load. The two numbers answer different questions and they do not cancel each other out. A feeder carrying a continuous 60 kVA load is already calculated at 75 kVA before any growth allowance is added, so a transformer bought at exactly 75 kVA starts with nothing in reserve for the equipment installed the following year.

Keeping the two figures separate is what makes the decision defensible afterwards. Record the connected load, the power factor it was measured or assumed at, and the growth percentage applied. If the transformer turns out to be too small in three years, that record is what distinguishes a load that grew from an estimate that was wrong at the start — and those two failures call for different fixes.

What the calculation does not cover

How this calculator is verified

Standard kVA ratings on this page and in the tables above follow the sizes the US distribution-transformer efficiency rules are written around, quoted separately for single-phase and three-phase. Full-load currents are derived directly from the kVA rating and voltage using the standard three-phase formula, and every cell in the rating table was recomputed rather than copied. Protection sizing follows NEC 450.3(B) at 125% of primary full-load current.

Standard ratings, rating tables and worked examples last verified: 2 November 2026.

Instruments and hardware for transformer work

Sizing is arithmetic, but the design load has to be measured and the installation has to be terminated correctly. These are the items that job needs.

  • Clamp meter — The connected load is the starting point. Measuring actual running current beats trusting a nameplate that may be conservative or wrong.
  • Power quality analyzer — Power factor is what converts the load to kVA. An analyzer gives the true figure for the design load, including the harmonic content a standard transformer may not tolerate.
  • Infrared thermometer — A transformer running hot points to a sizing or loading problem. A thermal check confirms the loading without opening the enclosure.
  • Torque screwdriver — Transformer and lug terminations have specified torque values. A torque screwdriver is how you meet them.

As an Amazon Associate I earn from qualifying purchases. The links above are affiliate links — if you buy through one, the price you pay is unchanged and a small commission helps keep these calculators free. Tools are listed because the job calls for them, not because of commission rates.

FAQ

How do I size a transformer?

Convert the connected load to kVA by dividing the real power in kW by the power factor, add a growth margin, then select the next standard kVA rating above that figure. Never round down to the nearest standard size.

Why are transformers rated in kVA instead of kW?

Because transformer heating depends on current and voltage independently of the phase relationship between them. Resistive winding losses depend on current and core losses depend on voltage, so apparent power determines the thermal limit regardless of the load power factor.

How do I calculate transformer full-load current?

For three-phase, amps equal kVA times 1000 divided by the square root of 3 times the line voltage. For single-phase, amps equal kVA times 1000 divided by the voltage. A 75 kVA transformer at 480 V three-phase carries 90 A.

What size transformer for a 200 amp service?

At 208 V three-phase, 200 A corresponds to about 72 kVA, so a 75 kVA transformer is the standard choice. At 240 V single-phase, 200 A is 48 kVA, making 50 kVA the nearest standard size.

How much growth margin should I allow?

Twenty to twenty-five percent is typical for commercial and light industrial work where some future load growth is plausible. Where the load is well understood and unlikely to change, ten percent is defensible, but transformers are difficult and disruptive to replace, so erring upward is usually cheaper in the long run.

What is a K-rated transformer?

A transformer designed to tolerate harmonic currents without overheating. Standard transformers are rated for linear loads; where a significant share of the load consists of variable frequency drives or switch-mode power supplies, harmonic losses concentrate in the windings and a K-rated unit is specified instead.

Does the power factor affect transformer sizing?

Yes, substantially. The same real load needs a larger transformer at a lower power factor. A 100 kW load requires 105 kVA at 0.95 but 143 kVA at 0.70, which is a difference of nearly two standard sizes.

What size primary protection does a transformer need?

Under NEC 450.3(B), for a transformer with a primary current of 9 A or more, protection at up to 125% of primary full-load current is permitted where only primary protection is provided. Where both primary and secondary protection are used, the percentages change. Always confirm the rule that applies to your configuration.

Should I use a single large transformer or several smaller ones?

Several smaller units closer to their loads reduce secondary cable lengths, reduce fault current at any one point, and give some redundancy. A single large unit is cheaper to buy and easier to maintain. The decision usually comes down to distribution losses against capital cost.

Why does the calculator return a size that is not on the three-phase list?

Because its internal rating list merges the single-phase and three-phase series, and between 15 kVA and 100 kVA the values it steps through are the single-phase ones. For a three-phase load in that band, take the kVA figure the calculator prints and round it up on the three-phase column: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750 and 1000 kVA. The full-load currents it reports are computed from the rating it selected, so re-run it with the corrected rating to get currents and protection that match the unit you actually buy.

More electrical tools

Have a suggestion?

Missing a feature or found something off? Tell us — user suggestions decide what we build next.