Voltage Drop Calculator — Copper & Aluminium, AC and DC

Work out the volts lost along a run, the voltage that actually reaches the load, and the largest conductor size you still need.

Voltage drop calculator

Code reference. The 3% and 5% figures used here come from the informational notes to NEC 210.19(A) and 215.2(A): branch circuits should be sized so the drop does not exceed 3%, and the total of feeder plus branch circuit should not exceed 5% for reasonable efficiency of operation. These are recommendations rather than mandatory limits, but they are what an inspector and a plan reviewer will expect to see.

What this calculator answers

Voltage drop is the amount of voltage lost as current travels through a conductor's own resistance. You enter the source voltage, the load current, the one-way length of the run, the conductor material and size, and the calculator returns the volts lost, the drop as a percentage, the voltage that actually arrives at the load, and the smallest conductor size that meets your chosen limit.

It also works backwards: it reports the longest run the selected conductor can carry before the drop exceeds the limit. That is often the more useful number, because cable size is usually fixed by the load and the length is what you are still deciding.

The formula behind the answer

For DC and single-phase AC circuits the standard approximation is:

Vd = 2 × K × I × L ÷ CM

and for a balanced three-phase circuit the factor of 2 becomes the square root of 3:

Vd = √3 × K × I × L ÷ CM

Where I is the load current in amperes, L is the one-way length in feet, CM is the conductor's cross-sectional area in circular mils, and K is the resistivity constant of the conductor material. The factor of 2 is there because current has to travel out to the load and back again, so the effective conductor length in a single-phase circuit is twice the physical distance.

The percentage drop is then simply Vd ÷ V × 100.

Why copper and aluminium give different answers

The K constant is the resistance of a one-foot length of conductor with a cross-section of one circular mil, and it changes with both material and temperature. At the 75°C conductor temperature that most modern terminations are rated for:

MaterialK (ohm-cmil/ft)Practical effect
Copper12.9Reference performance; smaller and more flexible
Aluminium21.2About 64% more resistance, so roughly two trade sizes larger

Aluminium is not a poor conductor — it is a lighter and cheaper one. For the same ampacity an aluminium conductor needs to be about two trade sizes larger than copper, and it needs terminations listed for aluminium. Where weight matters, such as a long service drop, aluminium frequently wins. Where space matters, copper usually does.

What counts as acceptable drop

CircuitRecommended maximumSource
Branch circuit3%NEC 210.19(A) informational note
Feeder plus branch, combined5%NEC 215.2(A) informational note
Voltage drop across a motor runningDo not exceed 5% at the motor terminalsIndustry practice; NEMA guidance
Sensitive electronics, medical, dataOften specified at 2% or lessEquipment manufacturer requirements

Two practical notes. First, a drop that is legal is not automatically a good idea: a compressor that starts at 90% of nameplate voltage draws more current and runs hotter, which shortens its life even though nothing has tripped. Second, long runs feeding modern LED drivers and switch-mode power supplies can behave worse than the simple calculation suggests, because those loads are non-linear. When in doubt, size up one trade size.

Three worked examples

1. A 120 V receptacle 100 ft from the panel

A 20 A continuous load on a 120 V single-phase circuit, 100 ft of one-way run, copper conductor. With 12 AWG the drop works out at about 7.9 V, or 6.6% — well outside the 3% target, even though 12 AWG is the correct size for a 20 A circuit on ampacity grounds alone. Moving to 8 AWG brings the drop to roughly 2.0 V, or 1.7%. This is the single most common surprise in residential work: ampacity says 12 AWG, distance says something much larger.

2. A 480 V three-phase feeder

A 100 A load on a 480 V three-phase circuit running 250 ft. Because the voltage is four times higher, the same absolute drop is a quarter of the percentage. A 1/0 copper conductor gives about 5.6 V, or 1.2%. At 480 V you can run a long way before voltage drop becomes the deciding factor — which is exactly why industrial installations use higher distribution voltages.

3. A 24 V DC circuit for a pump

A 10 A load on a 24 V DC circuit 50 ft away. DC uses the same factor of 2 as single-phase. With 10 AWG the drop is about 1.25 V, or 5.2%. That is already past the usual 3% target, so 8 AWG is the practical choice at about 3.1%. Low-voltage DC systems are unforgiving: the lower the voltage, the more the same absolute loss matters as a percentage.

Four mistakes this calculation catches

  1. Sizing on ampacity alone. Ampacity tables tell you what will not overheat the conductor. They say nothing about whether the equipment at the far end will still work. Both checks are required.
  2. Using the one-way length twice. Enter the one-way distance. The calculator applies the return-path factor itself. Doubling it manually is a common and expensive error.
  3. Assuming three-phase uses the same factor. Three-phase uses √3 rather than 2, which makes the drop about 13% lower for the same conductor and current. Using the wrong factor overstates the drop and leads to needlessly large cable.
  4. Forgetting that K depends on temperature. A conductor operating at 90°C has higher resistance than one at 75°C. The calculator uses 75°C values, which is the usual termination rating in modern equipment.

How this calculator is verified

The resistance constant K and the circular-mil areas follow the values published in the NEC Chapter 9 tables and standard conductor tables. The simplified K method is the one used in practice for feeder and branch-circuit sizing; it neglects AC reactance, power factor, conduit effects and temperature correction, which matters for very large conductors and for circuits with a low power factor.

  • NFPA 70, National Electrical Code — Article 210.19(A), Article 215.2(A), Chapter 9 Table 8 and Table 9.
  • NEMA — motor terminal voltage tolerance guidance (motors are normally rated for a 10% voltage variation).
  • OSHA electrical standards — workplace requirements that reference the NEC for installation methods.

Conductor tables, constants and worked examples last verified: 19 September 2026.

FAQ

What is an acceptable voltage drop?

The NEC informational notes recommend a maximum of 3% on a branch circuit and 5% for a feeder and branch circuit combined. Motor terminals should not see more than about 5% drop under running conditions. Sensitive electronic and medical equipment is often specified at 2% or less.

How do I calculate voltage drop?

For DC or single-phase use Vd = 2 x K x I x L divided by CM, where K is 12.9 for copper and 21.2 for aluminium, I is the current in amps, L is the one-way length in feet, and CM is the conductor area in circular mils. For three-phase, replace the 2 with the square root of 3, roughly 1.732. Then divide Vd by the source voltage and multiply by 100 for the percentage.

Does voltage drop apply to short runs?

Yes, but the percentage falls in proportion to length. A 20 A load at 120 V over 20 feet with 12 AWG copper drops only about 1.3%. The same load at 100 feet drops about 6.6%. Short runs are almost never limited by voltage drop; long ones almost always are.

Why does three-phase have less voltage drop than single-phase?

In a balanced three-phase circuit the return current is carried by the other two phases rather than by a dedicated neutral conductor, so less conductor length is effectively involved. The standard formula therefore uses the square root of 3 as the multiplier instead of 2, giving roughly 13% less drop for the same conductor and current.

How many circular mils is 12 AWG wire?

12 AWG has an area of 6,530 circular mils. For reference: 14 AWG is 4,110, 10 AWG is 10,380, 8 AWG is 16,510 and 6 AWG is 26,240 circular mils. Above 4/0 the sizes are stated directly in kcmil, so 250 kcmil is simply 250,000 circular mils.

Is aluminium wire worse for voltage drop?

It has about 64% higher resistance than copper, so a given size drops more voltage. Aluminium conductors are therefore usually specified about two trade sizes larger than the copper equivalent. Aluminium is lighter and cheaper, which makes it attractive for long service entrances and utility work.

Does temperature affect voltage drop?

Yes. Conductor resistance rises with temperature, so a conductor running at 90 degrees Celsius drops more voltage than the same conductor at 60 degrees. This calculator uses the 75 degrees Celsius resistance constants, which match the temperature rating of most modern terminations and lugs.

Why did my inspector ask for larger wire than the ampacity table requires?

Because ampacity and voltage drop are two separate requirements. The ampacity table ensures the conductor will not overheat. Voltage drop ensures the equipment at the end of the run still receives usable voltage. A long run can pass the first test and fail the second by a wide margin.

Can I reduce voltage drop without buying larger cable?

Yes, in three ways: reduce the current by splitting the load across more circuits, shorten the run by relocating the equipment or the supply, or raise the system voltage. Raising the voltage is the most effective single change, because the percentage drop falls in direct proportion.

Does this calculator work for DC solar and battery systems?

Yes. Choose DC as the system type and enter the one-way conductor length. DC uses the same factor of 2 as single-phase AC. Low-voltage DC systems are very sensitive to voltage drop, which is why solar designers often keep array-to-controller runs short or use a higher array voltage.

More electrical tools

Have a suggestion?

Missing a feature or found something off? Tell us — user suggestions decide what we build next.